Note:
• Different drive models have different wiring cover shapes.
• Clip only the areas from the wiring cover that apply to the wired terminal. If you clip areas that do not apply to wired
terminals, the drive will not keep its IP20 protective level.
• When you clip pieces of the cutaway section, tightly hold the cutaway section. Pieces of the cutaway section can fly out and
cause injury.
• Make sure that the clipped section does not cause damage to the wires.
• Although the wiring cover is correct, if you use wires that are not specified by Yaskawa, the drive will not keep its IP20
protective level.
• When you use the recommended gauge for the electrical wires, it is not necessary to attach the wiring cover of the main
circuit power input terminal and the drive output terminal. When you use the applicable gauge for the electrical wires, attach
the wiring cover.
6.
Attach the wiring cover and terminal block cover to their initial positions and tighten the screws on the
terminal block cover.
7.
Put the terminal cover back in its initial position.
YASKAWA SIEPC71061705H GA700 Series Technical Manual
3.4 Main Circuit Terminal Block Wiring Procedure
Figure 3.34 Reattach the Wiring Cover