12.8 H: Terminal Functions
A - H2-30
[Comparator 2 On-Delay Time]
Note:
The drive compares the monitors set with H2-26 as absolute values.
69: External Power 24V Supply
Setting Value
Function
69
External Power 24V Supply
ON : The external 24V power supply is supplying power.
OFF : The external 24V power supply is not supplying power.
6A: Data Logger Error
Setting Value
Function
6A
Data Logger Error
90 to 93: DWEZ Digital Outputs 1 to 4
Setting Value
Function
90 to 93
DWEZ Digital Outputs 1 to
4
A0 to A7: DWEZ Extended Digital Outputs 1 to 8
Setting Value
Function
A0 to A7
DWEZ Extended Digital
Outputs 1 to 8
100 to 1A7: Inverse Outputs of 0 to A7
Setting Value
Function
100 to 1A7
Inverse Outputs of 0 to A7
For example, set H2-xx = 10E for the inverse output of E [Fault].

H3: Analog Inputs

WARNING! Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are
correct. If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
Drives have three analog input terminals, terminals A1, A2, and A3. H3 parameters select the functions set to
these analog input terminals and adjust signal levels.
Table 12.69
shows the functions that you can set to analog input terminals. Use H3-02, H3-06, and H3-10 [MFAI
Function Selection] to set functions.
844
Figure 12.105 Comparator 2 Output Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when there is an external 24V power supply between terminals PS-AC.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the digital output for the DriveWorksEZ DO-A3 option card. Refer to the DriveWorksEZ online manual for more
information.
V/f
CL-V/f
OLV
CLV
AOLV
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function to
inversely output.
B - H2-31
[Comparator 2 Off-Delay Time]
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061705H GA700 Series Technical Manual