YASKAWA GA700 Series Technical Manual page 1003

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

◼ o5 -18:Analog Trigger Level
No.
Name
( Hex.)
o5-18
Analog Trigger
(1E85)
Level
RUN
◼ o5 -19: Trigger Condition
No.
Name
( Hex.)
o5-19
Trigger Condition
(1E86)
RUN
0 : Rising Edge
For a digital trigger, the trigger is detected when the digital trigger target switches from OFF
to ON. For an analog trigger, the trigger is detected when the analog trigger target changes
from less than the trigger level to greater than or equal to the trigger level.
1 : Falling Edge
For a digital trigger, the trigger is detected when the digital trigger target switches from ON
to OFF. For an analog trigger, the trigger is detected when the analog trigger target
changes from more than the trigger level to less than or equal to the trigger level.
◼ o5 -20: Pre-Trigger Setting
No.
Name
( Hex.)
o5-20
Pre-Trigger
(1E87)
Setting
RUN
◼ o5 -21: Trend Log Sampling Time Selection
No.
Name
( Hex.)
o5-21
Trend Log
(1E88)
Sampling Time
RUN
Selection
0 : Trend Log Disabled
The trend log is not saved.
1 : 0.1 s (About 1 hour)
Saves a trend log with a sampling cycle of 0.1 s. A maximum of approximately one hour of
data is saved before the trigger is detected.
2 : 1 s (About 10 hours)
Saves a trend log with a sampling cycle of 1 s. A maximum of approximately 10 hours of
data is saved before the trigger is detected.
3 : 10 s (About 100 hours)
Saves a trend log with a sampling cycle of 10 s. A maximum of approximately 100 hours of
data is saved before the trigger is detected.
4 : 60 s (About 600 hours)
Saves a trend log with a sampling cycle of 60 s. A maximum of approximately 600 hours of
data is saved before the trigger is detected.
De scription
V / f
C L - V / f
O LV
CLV A OLV O L V / P M
Sets the level to compare with the analog trigger target.
This parameter is only available when using an LCD
keypad.
De scription
V / f
C L - V / f
O LV
CLV A OLV O L V / P M
Selects the condition with which to detect the trigger.
This parameter is only available when using an LCD
keypad.
De scription
V / f
C L - V / f
O LV
CLV A OLV O L V / P M
Sets the percentage of data to save before the trigger is
detected for the short-term data log. This parameter is
only available when using an LCD keypad.
De scription
V / f
C L - V / f
O LV
CLV A OLV O L V / P M
Selects the sampling cycle for the trend log to save data
before the trigger is detected. The trend log works
concurrently with the short-term data log. This
parameter is only available when using an LCD keypad.
A O L V / P M C L V / P M
E Z O L V
(-999.9% - +999.9%)
A O L V / P M C L V / P M
E Z O L V
A O L V / P M C L V / P M
E Z O L V
A O L V / P M C L V / P M
E Z O L V
D ocu ment No. E ZZ024048<1>
P r epared in October, 2021
De fault
( Range)
0.0%
De fault
( Range)
0
(0 - 1)
De fault
( Range)
90%
(0% - 100%)
De fault
( Range)
0
(0 - 4)
19 / 19