Ethercat Communication Alarm - Leadshine EL8-EC Series User Manual

Ac servo drive
Table of Contents

Advertisement

8.5 EtherCAT Communication Alarm

EtherCAT communication related alarms are erasable and will not be recorded in
alarm history.
Clearing EtherCAT communication alarm is similar to clearing servo driver alarm.
Please clear the alarm before switching to 402 machine state.
EtherCAT communication alarm however, relies on register clearance from the main
station. Can be solved according to following steps:
1、Set bit 4 of ESC control register 0x120 (error responder) to 1.
2、 The communication alarm can be cleared until the feedback of the ESC status code
register 0x134~0x135 is 0.
3、By setting bit 7 of 6040h to 1, switches state machine from fault to initialization
completion , No fault(Switch on disabled).
Main
Sub
Error
code
73
A
Cause
Poor master
performance
Single-unit drive has
problem
interfere
Main
Sub
Error
code
73
B
Cause
Poor master
performance
Single-unit drive has
problem
interfere
Display:
"Er
73A"
Error description: SyncManager2 lost
Diagnosis
--
Is it a single unit or multiple units together
in the network
Check the grounding and network wiring
quality
Display:
"Er
73b"
Error description: SYNC0 lost
Diagnosis
--
Is it a single unit or multiple units together
in the network
Check the grounding and network wiring
quality
User manual of EL8-EC***F AC Servo
Solution
Increase the alarm
threshold
Switch drive
Replace the network
cable
Solution
Increase threshold value
limit
Switch drive
Replace the network
cable
325

Advertisement

Table of Contents
loading

This manual is also suitable for:

El8-ec400El8-ec750El8-ec1000

Table of Contents