8 Selector Switch
While OFF:
While satisfying the condition: Enables the Selector Switch when the condition is satisfied.
Data Type:
Selects the type of data handled by the conditional expression for the input condition.
This option can only be configured if While satisfying the condition is selected for Trigger Type.
For details, refer to Chapter 2 "1.1 Available Data" on page 2-1.
Device Address: Specifies the bit device or the bit number of the word device to serve as the input condition.
This option can only be configured when While ON or While OFF is selected for Trigger Type.
Click
"5.1 Device Address Settings" on page 2-68.
Condition:
Specifies the conditional expression for the input condition.
This option can only be configured when While satisfying the condition is selected for Trigger
Type.
Click
configuration procedure, refer to Chapter 2 "5.2 Setting Conditional Expressions" on page 2-71.
Comment:
Used for entering a comment for the input condition. The maximum number is 80 characters.
Visible Condition
The Selector Switch is displayed while the condition is satisfied. The Selector Switch is hidden while the condition is
not satisfied.
Example: When Trigger Type is While ON and Device Address is LM0
While LM0 is 0, the condition is not satisfied and the Selector Switch is hidden.
While LM0 is 1, the condition is satisfied and the Selector Switch is displayed.
If a hidden Selector Switch is redisplayed on the screen when Read from Destination Device Address is
selected for Default Position on the General tab, the display position of the knob changes according to
the value of the device address configured for the channel. When Ch1, Ch2, or Ch3 is selected, the knob is
displayed at the same position as before it was hidden, regardless of the value of device address configured
for the channel.
8-154
Enables the Selector Switch when the value of device address is 0.
1
Value of
device address
0
Selector
Switch state
Enabled
Satisfied
Condition
Not satisfied
Selector
Switch state
Disabled
to display the Tag Editor. For the device address configuration procedure, refer to Chapter 2
to display the Trigger Condition Settings dialog box. For the conditional expression
LM0 :
0
Condition
Not
satisfied
LM0 : 1
Condition
Satisfied
WindO/I-NV4 User's Manual
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
MICRO/I
Hide
Show
Disabled
Enabled
Enabled
Disabled