IDEC MICRO/I HG4G-CJT22 F-B Series User Manual page 231

Micro/i operator interfaces for windo/i-nv4
Table of Contents

Advertisement

Analog Input Object
This object manages a Float32(F) numeric value. The MICRO/I can make arbitrary numeric values available to BACnet
devices. For example, use this object when handling analog values input with the analog input module, the measured
room temperature, and other analog values.
Properties List
(1): Read and write from BACnet devices
(2): Read and write from device addresses when properties are allocated to device addresses
R: Read-only, W: Write-only, R/W: Read and write, -: Not Read and write
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Units
Resolution
COV_Increment
*2
Property_List
*1 Character encoding is ISO 10646 (UTF-8), and the maximum size is 64 bytes.
*2 Cannot be displayed on WindO/I-NV4.
Data Type of Property
BACnetObjectIdentifier
*1
Character string
BACnetObjectType
Real number
*1
Character string
*1
Character string
BACnetStatus_Flags
BACnetEventState
BACnetReliability
Logical value
BACnetEngineeringUnits
Real number
Real number
BACnetARRAY[N] of type
BACnetPropertyIdentifier
WindO/I-NV4 User's Manual
(1)
(2)
R
-
Set a fixed value with WindO/I-NV4.
R
-
Set a fixed value with WindO/I-NV4.
R
-
Set a fixed value with WindO/I-NV4.
R
W
Refer to "Present_Value" on page 3-132.
R
-
Set a fixed value with WindO/I-NV4.
R
-
Set a fixed value with WindO/I-NV4.
R
R
Refer to "Status_Flags" on page 3-145.
R
-
Normal (fixed).
Indicates whether or not the value of
R
R/W
Present_Value is reliable.
R/W
R/W
Refer to "Out_Of_Service" on page 3-146.
R/W
-
Set the initial value with WindO/I-NV4.
R
-
Set a fixed value with WindO/I-NV4.
R/W
-
Refer to "COV_Increment" on page 3-145.
R
-
Cannot be edited with WindO/I-NV4.
7 BACnet Communication
Comments
3-125