Batch
Select this check box to batch output all the sampled data to the external memory device
Alarm Log data
Ch.No.
Message
Occurrence Time
1-1
Voltage drop
12/01/2011 12:00:05
1-2
Temperature abnormal
12/01/2011 12:01:09
1-1
Voltage drop
12/01/2011 12:02:00
1-3
Overcurrent
12/01/2011 12:30:21
1-1
Voltage drop
12/01/2011 12:45:36
All the data is saved on the external memory device
to 1. If a file with the same name already exists on the external memory device
maximum amount of output data is the amount configured by the data storage area.
The storing of data stops if there is insufficient free space on the external memory device. The error
information is stored in the following HMI Special Data Registers. For details about the error information,
refer to Chapter 33 "HMI Special Data Register (LSD)" on page 33-7.
SD memory card:
USB flash drive:
Trigger Device Address: Specifies the bit device or the bit number of the word device to serve as condition for batch
File Name:
*1 SD memory card for HG5G/4G/3G/2G-V, HG4G/3G and HG2G-5F, USB flash drive for HG2G-5T and HG1G/1P
Recovery Time
Confirmation Time
12/01 12:01:10
12/01 12:01:30
12/01 12:02:21
12/01 12:02:55
12/01 12:03:11
12/01 12:05:12
12/01 12:55:15
12/01 13:00:00
12/01 12:53:12
12/01 12:57:41
Data to be output (all)
*1
LSD42
LSD33
output. For the device address configuration procedure, refer to Chapter 2 "5.1 Device
Address Settings" on page 2-68.
Data is output to file when the value of the Trigger Device Address changes from 0 to 1.
Enter the file name for the output data or shows the file name.
The default is "ALMHTO.CSV". To change the file name, enter a new file name. The
maximum number is 120 characters (including the extension).
Specify File Name by Value of Device Address: Select this check box to assign a file name
(File Name Device Address):
Example: When the device address specified by (File Name Device Address) is LDR100
and the text to set is "IDEC":
(File Name Device Address)
The file name at this time becomes "IDEC.CSV".
WindO/I-NV4 User's Manual
MICRO/I
Trigger Device Address
0
1
when the value of the Trigger Device Address changes from 0
*1
, that file is overwritten. The
for the output data using a value of device
address specified in the File Name Device
Address.
Specifies a word device to create a file name. The file
name is set by reading the values sequentially from
the starting device specified with the File Name
Device Address and handling those values as
character data up to the character before NULL (00).
The maximum number of device addresses is 40 (2
characters per word device, maximum of 80 single-
byte characters). You can only specify an internal
device. For the device address configuration
procedure, refer to Chapter 2 "5.1 Device Address
Settings" on page 2-68.
LDR100
' I ' 'D'
LDR101
'E' 'C'
LDR102
(NULL)
3 Alarm Log Settings Dialog Box
*1
.
External Memory Device
SD memory card
Output to
USB flash drive
External memory device
Alarm Log data (CSV)
4844(Hex)
4543(Hex)
0000(Hex)
13-21