IDEC MICRO/I HG4G-CJT22 F-B Series User Manual page 236

Micro/i operator interfaces for windo/i-nv4
Table of Contents

Advertisement

7 BACnet Communication
Binary Value Object
This object can be used in the same manner as the Binary Input object and Binary Output object.
Properties List
(1): Read and write from BACnet devices
(2): Read and write from device addresses when properties are allocated to device addresses
R: Read-only, W: Write-only, R/W: Read and write, -: Not Read and write
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Status_Flags
Event_State
Reliability
Out_Of_Service
Priority_Array
Relinquish_Default
*2
Property_List
*1 Character encoding is ISO 10646 (UTF-8), and the maximum size is 64 bytes.
*2 Cannot be displayed on WindO/I-NV4.
3-130
Data Type of Property
BACnetObjectIdentifier
*1
Character string
BACnetObjectType
BACnetBinaryPV
*1
Character string
BACnetStatus_Flags
BACnetEventState
BACnetReliability
Logical value
BACnetPriority_Array
BACnetBinaryPV
BACnetARRAY[N] of type
BACnetPropertyIdentifier
WindO/I-NV4 User's Manual
(1)
(2)
R
-
Set a fixed value with WindO/I-NV4.
R
-
Set a fixed value with WindO/I-NV4.
R
-
Set a fixed value with WindO/I-NV4.
R
R
Refer to "Present_Value" on page 3-132.
R
-
Set a fixed value with WindO/I-NV4.
R
R
Refer to "Status_Flags" on page 3-145.
R
-
Normal (fixed).
Indicates whether or not the value of
R
R/W
Present_Value is reliable.
R/W
R/W
Refer to "Out_Of_Service" on page 3-146.
R/W
R/W
Refer to "Priority_Array" on page 3-145.
R/W
-
Refer to "Relinquish_Default" on page 3-145.
R
-
Cannot be edited with WindO/I-NV4.
Comments

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents