7 BACnet Communication

7.7 BACnet Settings Dialog Box

This section describes items on the BACnet Settings dialog box.
BACnet/IP Settings
Basic Settings
Device ID:
Port Number:
Turn ON BACnet Communication bit (LSM70) automatically:
When the following operations are performed, the value of the HMI Special Internal Relay LSM70 (BACnet
Communication Bit) changes to 0.
• Downloads the project data.
• Turns off the MICRO/I.
• Switches to System Mode.
*1 For Present_Value, refer to "7.8 Objects" on page 3-124 and "Present_Value" on page 3-132.
*2 For Status_Flags, refer to "7.8 Objects" on page 3-124 and "Status_Flags" on page 3-145.
3-108
The assigned ID used to identify BACnet devices on the BACnet/IP network. Configures the
device ID in the range from 1 to 4,194,302.
Fixed Value:
Use a constant value. (Default: 4194301)
Data Register:
Uses a value of device address.
This option uses 2 words of address numbers starting from the specified
data register.
Configures the port number for performing BACnet Communication. Configures the port number
in the range from 0 to 65,535.
Fixed Value:
Use a constant value. (Default: 47808)
Data Register:
Uses a value of device address.
Configures whether or not to set 1 to the HMI Special Internal Relay LSM70 (BACnet
Communication Bit) in the END processing of the first scan when starting operation.
LSM70 Status
BACnet/IP
1
Enabled
0
Disabled
WindO/I-NV4 User's Manual
*1
Present_Value
and
Device Address Value
Bound
Not bound
Overridden Flag in
*2
Status_Flags
FALSE