Advanced Usage - IDEC MICRO/I HG4G-CJT22 F-B Series User Manual

Micro/i operator interfaces for windo/i-nv4
Table of Contents

Advertisement

1 Numerical Input
Without Pressing the Numerical Input, Directly Entering Values from a Keypad on the Same Screen
Arrange a Numerical Input and a keypad on the same screen. In the properties dialog box for the Numerical Input, on
the General tab, under Keypad, select Current Screen for Type and select the Always Entry Mode check box.
Display value of device address
(Entry mode)
Display value of device address
(Entry mode)
Display value of device address
(Entry mode)

1.5 Advanced Usage

Using the System Area
• When finished entering a value by pressing ENT, 1 is written to the System Area 2 Numerical Input Setting
Complete bit (address number+3, bit 0).
If the System Area 2 Numerical Input Setting Complete Bit (address number+3, bit 0) is set to another
function's execution condition, that function can be executed when ENT is pressed.
Example: To simultaneously close a popup screen when ENT is pressed
• When CAN is pressed, entry mode is canceled and 1 is written to the System Area 2 Numerical Input Setting
Cancel bit (address number+3, bit 1). However, if the keypad is closed by pressing
screen's title bar or another Numerical Input is pressed before finished entering the value by pressing ENT, entry
mode is canceled and 1 is not written to the System Area 2 Numerical Input Setting Cancel bit (address number+3,
bit 1).
• To clear the System Area 2 numerical input setting complete bit or the numerical input setting cancel bit, write 1 to
System Area 1 Numerical Input Setting Clear bit (address number+1, bit 10). To automatically clear these bits
when the Numerical Input keypad is pressed in entry mode, select the Clear Keypad bit in System Area
automatically check box on the System tab in the Project Settings dialog box.
10-26
MICRO/I
1234
999
999
In the Properties of Goto Screen Command dialog box, on the General tab, select Close Popup
Screen for Action Mode. On the Trigger Condition tab, select Rising-edge for Trigger
Type, and configure Device Address as the System Area 2 Numerical Input Setting Complete bit
(address number+3, bit 0).
WindO/I-NV4 User's Manual
External device
Enter "999"
Write value
to device address
Press ENT
D100:
1234
D100:
999
D100:
999
(close) on the popup