Status_Flags
This property represents the current status of the object (in alarm, fault, out of service, etc.).
Status_Flags
Value
0
*1
IN_ALARM
1
0
FAULT
1
0
*1
OVERRIDDEN
1
0
OUT_OF_SERVICE
1
The allocation of flags in the device address is as follows.
Bit
Bits 15 to 8
Bit 7
Bit 6
Bit 5
Bit 4
Bits 3 to 0
COV_Increment
This property represents the minimum amount of change in Present_Value.
COV notifications are sent when the value of Present_Value for the COV notification that was last sent changes to a
value that is greater than or equal to the value set with COV_Increment. COV_Increment cannot be read out to device
address. Set the initial value with WindO/I-NV4.
Priority_Array
Priority_Array is a read-only property representing the array that stores the priority values.
Of the 16 elements in the array (element 1 to element 16), the value stored in Priority_Array with the smallest index
number out of all non-NULL(00h) values is used as the value of Present_Value. If all values stored in Priority_Array
are NULL(00h), Relinquish_Default is used as Present_Value.
Relinquish_Default
Relinquish_Default is the default value used as Present_Value when all values stored in Priority_Array are NULL(00h).
Polarity
This property represents the relationship between the physical state of the input/output and the logical state
indicated by Present_Value in the Binary Input and Binary Output objects.
Polarity
NORMAL
NORMAL
REVERSE
REVERSE
*1 Always FALSE on the MICRO/I.
Logical Value
FALSE
When obtaining a value where Event State is Normal.
TRUE
Other than above
FALSE
Other than below
TRUE
When Reliability is present and the no-fault-detected value is not obtained
FALSE
Other than below
TRUE
Present_Value and Reliability did not follow the change in physical input
FALSE
When Out_Of_Service is TRUE
TRUE
When Out_Of_Service is FALSE
Flag
Reserved
IN_ALARM
FAULT
OVERRIDDEN
OUT_OF_SERVICE
Reserved
Physical State of Input/
Output
OFF or INACTIVE
ON or ACTIVE
ON or ACTIVE
OFF or INACTIVE
WindO/I-NV4 User's Manual
Condition
Undefined
0 (fixed)
0 or 1
0 (fixed)
0 or 1
Undefined
Present_Value
INACTIVE
ACTIVE
INACTIVE
ACTIVE
7 BACnet Communication
Value
Physical State of Device
Not running
Running
Not running
Running
3-145
3