Storage Method of 32-bit Numerical Data for Internal Devices
Selects the handling method for values of internal devices when UBIN32(D), BIN32(L), BCD8(EB), or Float32(F)
is selected for Data Type from the following. The initial value is set according to the communication driver that was
selected when the project was created. When the bit devices in control devices are handled as words, this setting is
always the from Lower word.
from Upper word:
from Lower word:
Use Large Password Screen
Select this check box to display the Password Screen at a large size.
*3 HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F only
Values of internal devices are read from and written to the upper order word.
Example: When Data Type for the Numerical Input is UBIN32(D) and the numerical
value 12345678 (Hex) was entered and written to destination device address
LDR100
Device address
Stored value
LDR100
1234 (Hex)
LDR101
5678 (Hex)
Values of internal devices are read from and written to the lower order word.
Example: When Data Type for the Numerical Input is UBIN32(D) and the numerical
value 12345678 (Hex) was entered and written to destination device address
LDR100
Device address
Stored value
LDR100
5678 (Hex)
LDR101
1234 (Hex)
*3
WindO/I-NV4 User's Manual
3 Project Settings Dialog Box
Upper word
Lower word
Upper word
Lower word
4
4-29