Settings
The Alarm Log settings for each channel are edited here.
No.:
Displayed as (Block No.)-(Channel No.). Double clicking the cell opens the Individual Settings
dialog box.
Source:
Shows the bit device or the bit number of the word device to monitor. Double clicking the cell
opens the Tag Editor.
For the device address configuration procedure, refer to Chapter 2 "5.1 Device Address
Settings" on page 2-68.
Data:
Shows whether or not to save Alarm Log data in the date storage area.
Double clicking the cell switches between Store and No Store.
Setting to Store makes the buzzer sound when the value of bit for the channel changes to 1.
Alarm function:
Shows whether or not the alarm function is used. Double clicking the cell switches between
Enable and Disable. Channels switched to Disable cannot be configured. States of device
addresses are not monitored and Alarm Log data is not created.
NO/NC:
Shows the alarm detection condition. Double clicking the cell switches between NO and NC.
Lock/Unlock:
Shows whether or not to automatically recover based on the state of the monitored bit.
Double clicking the cell switches between Lock and Unlock.
Text ID:
Shows the Text Manager ID number (1 to 32000) to use for the message displayed when an
alarm occurs. Double clicking the cell allows you to specify the Text Manager ID number.
Text Message:
Shows the text for the specified text ID. Double clicking the cell opens the Text Manager.
Reference Screen No.: Shows the screen number to display when the key button Ref. is pressed. Double clicking the
cell opens the Individual Settings dialog box.
This option can only be configured when Base Screen or Popup Screen is selected in
Reference Screen.
Auto
Batch registers or changes the settings for all the channels.
Click this button to open the Auto-Setup dialog box. The Auto-Setup dialog box settings are reflected in all the
channels.
For details, refer to "Auto-Setup Dialog Box and Individual Settings Dialog Box" on page 13-18.
Edit
Registers or changes the settings for the selected channel.
Select a channel and click this button to open the Individual Settings dialog box. The settings for the selected channel
are reflected in the Individual Settings dialog box.
For details, refer to "Auto-Setup Dialog Box and Individual Settings Dialog Box" on page 13-18.
WindO/I-NV4 User's Manual
3 Alarm Log Settings Dialog Box