Channel Settings
The trigger condition for the channel is configured here.
Alarm function:
Selects whether or not to use the alarm function.
Enable:
Disable:
NO/NC:
Selects the alarm detection condition.
NO:
NC:
Lock/Unlock:
Selects whether or not to automatically recover based on the state of the monitored bit.
Lock:
Unlock:
Example: NO/NC is NO
The display on the Alarm List Display disappears when the alarm is recovered from, regardless of the Lock/
Unlock setting. To keep displaying the alarm until CHECK is pressed, use the Alarm Log Display.
Text ID:
Text:
Reference Screen Number: Specifies the screen number (1 to 3000) to display when the key button Ref. is pressed.
Monitors the state of the device address configured for the channel and samples
the alarm information.
Does not monitor the state of the device address. No Alarm Log data is created.
The alarm occurs when the monitored bit changes from 0 to 1.
The alarm occurs when the monitored bit changes from 1 to 0.
Even if the monitored bit returns the normal state, the alarm remains active until
the key button CHECK is pressed.
The alarm is automatically recovered from based on the bit state when the
monitored bit returns the normal state.
Monitored bit
0
Alarm occurred
0
Press CHECK
To use text registered in Text Manager as the message to display when an alarm occurs,
select this check box and specify the Text Manager ID number to use as the message.
Number of blocks x 16 (number of channels) text IDs are used starting from the set ID
number.
Click
to open Text Manager where you can edit the text.
Shows the text for the specified text ID.
Number of blocks x 16 (number of channels) screens are used starting from the screen
number.
This option can only be configured when Base Screen or Popup Screen is selected in
Reference Screen.
WindO/I-NV4 User's Manual
3 Alarm Log Settings Dialog Box
Unlock
1
Record occurrence me
1
Record recovery me
Record confirma on me
Lock
Record occurrence me
No opera on
Record confirma on me
Record recovery me
13