IDEC MICRO/I HG4G-CJT22 F-B Series User Manual page 296

Micro/i operator interfaces for windo/i-nv4
Table of Contents

Advertisement

3 Project Settings Dialog Box
When Protocol1 to Protocol7 is selected for Ethernet under Interface Configuration
Function:
Selects the user communication to configure for the selected function from the following.
External Device Communication 1, External Device Communication 2, External Device
Communication 3, External Device Communication 4
User Communication 1, User Communication 2, User Communication 3
Operation Mode:
Selects the operation mode when performing user communication with the Ethernet interface.
This option can only be configured when User Communication 1, User Communication 2, or User
Communication 3 is selected for Function.
TCP Client:
TCP Server:
*1
UDP
:
Target:
MICRO/I:
*1 HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F only
4-42
The MICRO/I operates as a TCP/IP client and the external device operates as a TCP server.
The MICRO/I connects to the TCP server and sends and receives data.
The MICRO/I operates as a TCP/IP server and the external device operates as a TCP client.
The MICRO/I creates a listening port as a TCP server and waits for connections from TCP
clients. After a connection, it sends and receives data with the TCP client.
The MICRO/I operates as a UDP server and client.
The MICRO/I sends data to the listening port of the external device. The external device
also sends data to the MICRO/I's listening port and that data is received by the MICRO/I.
Configures the IP address and port number for the external device.
These options can only be configured when TCP Client or UDP is selected for Operation
Mode.
IP Address: Specifies the IP address for the target.
The format is "xxx.xxx.xxx.xxx". "xxx" stands for a numeric value from 0 to
255.
When connecting multiple devices to the same network, make sure to assign
each device a unique IP address.
Specifies the port number for the target (0 to 65535).
Port No.
:
Change IP Address and Port Number by Device Address:
Select this check box and specify a word device to change the target's IP
address and port number during operation. You can only specify an internal
device. During the start of operation, the MICRO/I writes the values
configured by IP Address and Port No. to this device address. After the
start of operation, the value of device address is read and the target is
changed.
Click
to display the Tag Editor. For the device address configuration
procedure, refer to Chapter 2 "5.1 Device Address Settings" on page 2-68.
Example: When IP Address is set to 192.168.1.1, Port No. is 2105, and the
device address is LDR100
LDR100
LDR101
LDR102
LDR103
LDR104
Configures the MICRO/I listening port number.
These options can only be configured when TCP Server or UDP is selected for Operation
Mode.
Port No.:
Specifies the MICRO/I listening port number (0 to 65535).
WindO/I-NV4 User's Manual
2105
Port number
192
168
IP address
1
1