7 BACnet Communication

7.5 BACnet/IP Operation

BACnet/IP is enabled and disabled according to the value of HMI Special Internal Relay LSM70 (BACnet
Communication Bit).
Properties with allocated device addresses work by referencing those device addresses.
When BACnet/IP is enabled and properties or the values of device addresses that are associated with properties are
changed, they operate with the values after the change.
BACnet/IP
Enabled
Disabled
When the status of the BACnet communication is stopped by error (the value of HMI Special Data Registers
LSD260-3 is 1) and restarts the BACnet communication, set 0 to the value of HMI Special Internal Relay
LSM70, and then set 1 to the value of HMI Special Internal Relay LSM70 after the status of the BACnet
communication is stopped (the value of HMI Special Data Registers LSD260-0 is 1).
3-104
Properties with Allocated Device Addresses
and the Values of Those Device Addresses
Bound
Not bound
WindO/I-NV4 User's Manual