Device Communication Control Password:
Configures the password to request when the Device Communication Control service is received
from a BACnet device. The maximum number is 20 characters. When the Device Communication
Control service is received, the MICRO/I does not initiate a service or provide a response for the
specified period of time.
COV Settings
Unsubscribed COV Frequency (sec):
Configures the cycle to regularly provide notifications of property values with the COVU function
as 1 to 65,535 (seconds). If 0 is set, the COVU function is stopped, and notification is provided
only when there is a change in the target property.
Fixed Value:
Data Register:
• Only one Unsubscribed COV frequency can be set for the MICRO/I, and different frequencies cannot be
set per object.
• Whether or not to use the COVU function can be selected per object. The COVU function can also be
enabled and disabled by specifying a data register and changing its value.
• When changing the value of the data register, the Unsubscribed COV frequency after it has been changed
will be applied after the service is next initiated.
Foreign Device Settings
Enable Foreign Device:
BBMD IP Address:
BBMD Port Number:
Lifetime (sec):
Registration Trigger Device: The device address used to register the MICRO/I with the BBMD configure with BBMD
Use a constant value. (Default: 60 sec)
Uses a value of device address.
Configures whether or not to use the Foreign Device function.Using the Foreign Device
function, the MICRO/I registers itself as a Foreign Device on the configure BBMD.
To join a BACnet/IP network when there is no BBMD on the IP subnet of the MICRO/I,
configures the IP address of the BBMD on the other IP subnet.
Fixed Value:
Use a constant value.
Data Register: Uses a value of device address.
This option uses 4 words of address numbers starting from the specified
data register.
Example: Configures 192.168.2.5 to the IP address of the BBMD.
The address number of Top Device Address+0 = 192
The address number of Top Device Address+1 = 168
The address number of Top Device Address+2 = 2
The address number of Top Device Address+3 = 5
To join a BACnet/IP network when there is no BBMD on the IP subnet of the MICRO/I,
configures the port number of BBMD on other IP subnet from 1 to 65,535.
Fixed Value:
Use a constant value. (Default: 47808)
Data Register: Uses a value of device address.
Configures the interval of time to register the MICRO/I with the BBMD as a Foreign
Device in the range from 0 to 65,535 (seconds). (Default: 360 sec)
When (Lifetime + 30) sec has elapsed from registration, the registered content will be
deleted from the BBMD.
IP Address above as a Foreign Device. When the value of the Registration Trigger
Device is changed from 0 to 1, the MICRO/I is registered with the BBMD. To
continuously register the MICRO/I with the BBMD, use the Registration Trigger
Device to re-register the MICRO/I before (Lifetime + 30) sec elapses.
WindO/I-NV4 User's Manual
7 BACnet Communication
3-109