Constant (Hexadecimal)
The received data is considered as hexadecimal data and compared with the data specified without being converted.
Use this setting to receive a control code of ASCII data (00h to 1Fh).
This can be configured only when RXD is selected as Type on the Command Settings dialog box, and Constant
(Hexadecimal) is selected under Type on the Data Settings dialog box.
Data
Enter hexadecimal data designated to be received (1 to 1,500 bytes).
When a Constant (Character) is set at the beginning of a command, the first one byte is recognized as the
start code. When a Constant (Character) is set at the end of a command, the last one byte is recognized as
the terminal code.
For details, refer to "Start Code and Terminal Code" on page 3-78.
Example: Constant (Hexadecimal) for receive command data
Item
Data
When the trigger condition is satisfied, the received data is compared with the following data.
Data used for comparison with received data
Specified data
1234h
No conversion
Setting
1234
12h
34h
Order of reception
WindO/I-NV4 User's Manual
5 User Communication
3
3-63