4 Using the Data

4.2 Displaying Data as Numerical Values

You can display data in the Numerical Display by copying data saved in the data storage area to an internal device
according to the conditions configured with the Options tab on the Individual Settings dialog box.
Copying Data to Internal Devices
Copying Sampling Time Data
Sampling time data is copied as a BCD value to the six sequential device addresses starting with the device address
configured by Destination Device Address.
The sampling time data is copied in year, month, day, hour, minute, second order regardless of the Stored Order of
Data setting.
Example
When the sampling time 10/01/2011 12:01:30 is copied to the destination device address
Data log data
Sampling Time
10/01/2011 12:01:30
Data Read Start Position and Copy Order of Data to the Destination Device Address
The data to copy and the order differs according to the Starting Point and the Stored Order for Data settings.
Example 1
Copying three items of the newest data in the Data Log to the destination device address
Item
Destination Device Address
Starting Point
Number of Data
Stored Order of Data
Newest data
read starting point
14-36
Value
Configured
20
device address
LDR10
Newest Data
3
From Newest to Oldest
Data log data
Sampling Time
Value
12/18/2011 17:44:10
20
:
:
12/19/2011 19:24:43
22
12/19/2011 20:01:54
24
12/19/2011 21:39:21
26
12/20/2011 05:57:06
28
Amount of data: 3
WindO/I-NV4 User's Manual
Destination Device Address Value
LDR10
LDR11
LDR12
LDR13
LDR14
LDR15
Setting
Destination Device Address Value
Configured
LDR10
device address
LDR11
LDR12
2011
Year
10
Month
1
Day
12
Hour
1
Minute
30
Second
28
Copy from
newest data
26
24

Hide quick links:

Advertisement

Table of Contents
loading