16.4 GOT Side Settings

16.4.1 Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: MITSUBISHI ELECTRIC
• Controller Type: Set according to the Controller
Type to be connected.
• I/F: Interface to be used
• Driver: MELSERVO-J4, J3, J2S/M, JE
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

16.4.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
16.4.2 Communication detail settings
Make the settings according to the usage environment.
3.
Item
4.
Transmission
Speed
Data Bit
Click!
Stop Bit
Parity
Retry
Timeout Time
Host Address
Delay Time
Station No.
Selection
POINT
POINT
POINT
(1) Communication interface setting by Utility
(2) Precedence in communication settings
16. SERVO AMPLIFIER CONNECTION
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 9600bps)
Set this item when change the data length
used for communication with the
connected equipment.
(Default: 8bit)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform a parity
check, and how it is performed during
communication.
(Default: Even)
Set the number of retries to be performed
when a communication timeout occurs.
(Default: 3times)
Set the time period for a communication to
time out.
(Default: 3sec)
Specify the station number of the servo
amplifier in the system configuration.
(Default: 0)
Set this item to adjust the transmission
timing of the communication request from
the GOT.
(Default: 0ms)
Specify whether to use the station No.
during communication.
If [Yes] is selected, the station No. is fixed
to "0."
(Default: Yes)
The communication interface setting can be
changed on the Utility's [Communication Settings]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GT
User's Manual
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
16.4 GOT Side Settings
9
10
11
Range
9600bps,
19200bps,
38400bps,
57600bps
115200bps
12
8bit (fixed)
1bit (fixed)
Even (fixed)
13
0 to 5times
3 to 30sec
0 to 31
14
0 to 300 (ms)
Yes or No
15
16
16 - 15