Mitsubishi Electric GT1685 Connection Manual page 478

Got1000 series
Table of Contents

Advertisement

(b) Station information setting
Item
Intelligent device station
Station type
*1
Exclusive station count
Reserve/invalid station
select
Intelligent buffer select
(word)
: Necessary
*1
Specify the same number of occupied stations as that of the
GOT.
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the PLC CPU,
operate the PLC CPU ether turning OFF and then ON
or resetting.
13 - 38
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
Setting
necessity at
Set value
GOT
connection
(fixed)
Exclusive station 1
No setting
(Use default value)
: As necessary
: Not necessary
(2) Setting from sequence program
The parameter is written to the buffer memory, and the
data link is automatically started when PLC CPU status
changes from STOP to RUN.
(a) I/O signal of CC-Link module
Control & Communication Link System Master/
Local Module Type AJ61QBT11/A1SJ61QBT11
User's Manual
(b) Device used by user
Device
M100, M101
Flag for parameter setting
M102, M103
Flag for data link startup
D0
Number of connected modules
D1
Number of retry
D2
Automatic reconnection station count
D3
Operation specification in the case of CPU failure
Reserved station specification (Station No. 1 to
D4
Station No. 16)
Error invalid station specification (Station No. 1 to
D5
Station No. 16)
D6
Station data (first module)
D400
Error code in the case of data link startup failure
(c) Buffer memory settings used in the present
example
Buffer memory
address
Decimal (Hex)
1(11 (1
)
Number of connected modules
H
2(22 (2
)
Number of retry
H
Automatic reconnection station
3(33 (3
)
H
count
Operation specification in the
6(66 (6
)
H
case of CPU failure
Reserved station specification
16(1016 (10
)
H
(Station No. 1 to Station No. 16)
Error invalid station specification
20(1420 (14
)
H
(Station No. 1 to Station No. 16)
32(2032 (20
)
Station data (first module)
H
*1
Details for the station data are shown below.
For 1) and 2), set the same station No. and number of station
occupied as those of the GOT.
For 3), the setting is fixed.
b15
to
b12 b11
to
3)
2)
1) Station No. (Set the same station No. as that of the GOT)
01
to 40
: Station No. 1 to Station No. 64
H
H
2) Number of stations occupied (Set the number of station
occupied as that of the GOT)
1
: Exclusive station 1
H
2
: Exclusive station 2
H
3
: Exclusive station 3
H
4
: Exclusive station 4
H
3) Station type (2
: Set it to intelligent device station)
H
0
: Remote I/O station
H
1
: Remote device station
H
2
: Intelligent device station (Incl. local station)
H
Application
Item
Set value
1 (1 module)
3 (3times)
1 (1 station)
0 (stop)
0 (No
specification)
0 (No
specification)
*1
2101
H
b8 b7
to
1)
b0