Plc Side Setting; Connecting To Melsec Iq-R Series - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

11.4 PLC Side Setting

This section describes the settings of the GOT and CC-
Link IE controller network module in the following case of
system configuration.
POINT
POINT
POINT
CC-Link IE Controller Network module
For details of the CC-Link IE Controller Network
module, refer to the following manual.
CC-Link IE Controller Network Reference
Manual
11.4.1
Connecting to MELSEC iQ-R
Series
 System configuration1
(Network Type: CC IE Control)
■ GT Designer3 [Communication settings] on System
configuration1 (Network Type: CC IE Control)
<GOT>
(Use the default value for settings other
than the following.)
CC-Link IE Controller Network
<CC-Link IE Controller Network module> *
(Use the default value for settings other than the following.)
Station No.
Mode
Network type
Network No.
Total stations
Network range assignment :
[Unit parameter] of GX Works3
*1
The CC-Link IE Controller Network module is mounted on
slot 0 of the base unit.
The start I/O No. of the CC-Link IE Controller Network
module is set at [0].
LB0100
to LB01FF
H
H
LW00100
to LW001FF
H
H
1
: 1
: Online
: CC IE Control (Control station)
: 1
: 2
LB0000
to LB00FF
H
H
LW00000
to LW000FF
H
H
11. CC-Link IE CONTROLLER NETWORK CONNECTION
 System configuration2
(Network Type: CC IE Control extended
mode)
<GOT>
(Use the default value for settings other
than the following.)
CC-Link IE Controller Network
<CC-Link IE Controller Network module> *
(Use the default value for settings other than the following.)
Station No.
Mode
Network type
Network No.
Total stations
Network range assignment :
*1
The CC-Link IE Controller Network module is mounted on
slot 0 of the base unit.
The start I/O No. of the CC-Link IE Controller Network
module is set at [0].
 Parameter settings (Connecting to MELSEC
iQ-R series) of System configuration1
(Network Type: CC IE Control)
(1) [Unit parameter] of GX Works3
(a) Unit parameter
Item
Station Type
Control Station (fixed)
*1
Network No.
Station Number Setting
Network Range
Assignment
: Necessary
*1
Specify the same network No. as that of the GOT.
11.4 PLC Side Setting
LB0100
to LB01FF
H
H
LW00100
to LW001FF
H
H
1
: 1
: Online
: CC IE Control extended mode
(Control station)
: 1
LB0000
to LB00FF
: 2
H
H
LW00000
to LW000FF
H
H
Setting
necessity at
Set value
GOT
connection
1
1
Refer to (b)
: As necessary
: Not necessary
11 - 11
9
10
11
12
13
14
15
16