Ethernet Connection (Connection To Ethernet Module Mounted On Remote I/O Station); Ethernet Connection - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

4.1.3
Ethernet connection (Connection to Ethernet module mounted on remote I/O
station)
This section explains the Ethernet connection for connecting the GOT to the Ethernet module mounted on the remote I/
O station of the MELSECNET/H network system.
The following shows an example of connecting the GOT to the Ethernet module mounted on the I/O station of the
MELESCNET/H network system.
Monitor target
Control system
(System A)
Network No. 1, Station No. 2
(remote I/O station)
(1) Connection method
Connect the GOT to the Ethernet module (QJ71E71-100, QJ71E71-B5, QJ71E71-B2, QJ71E71) mounted on
the remote I/O station of the MELSECNET/H network system.
For details, refer to the following.
(2) GT Designer3 setting
Set GT Designer3 as follows.
Setting item
Controller Type
Device setting (Network setting)
Q Redundant Setting
Routing Information Setting
*1
GT14 is not compatible with MELSEC-QS.
In this case, the GOT monitoring is performed by transient transmission of the MELSECNET/H network system.
Therefore, a longer time-lag occurs for displaying objects compared with directly monitoring the PLC CPU.
For displaying objects with a shorter time-lag, set the device for link devices B and W of the host station set in
the MELSECNET/H network and execute the cyclic transmission.
For details, refer to the following manual.
(3) Monitoring target change when system switching occurs in a redundant system
When the system switching occurs, the multiplexed remote sub master station switched to the control system
takes over the master operation of MELSECNET/H.
Since the GOT monitors the master station, the monitoring target is automatically changed to the PLC CPU that
is operating as the master.
4 - 10
4. HOW TO MONITOR REDUNTANT SYSTEM
4.1 Connection to Remote I/O Station in MELSECNET/H Network System
Network No. 1, Station No. 0
(Multiplexed remote master station)
MELSECNET/H remote I/O network

8. ETHERNET CONNECTION

GT16, GT15, GT12: MELSEC-QnA/Q/QS, MELDAS C6*
GT14: MELSEC-QnA/Q, MELDAS C6*
Other
Do not set the item.
8. ETHERNET CONNECTION
Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/Q network)
Network No. 1, Station No. 1
(Multiplexed remote sub master station)
Network No. 2, Station No. 2
Ethernet
Network No. 2, Station No. 3
GOT
Settings
*1
NW No.: Network No. of MELSECNET/H remote I/O network
Station No.: 0 (Master station)
Standby system
(System B)
Model