Got Side Settings; Setting Communication Interface (Communication Settings); Communication Detail Settings - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

17.3 GOT Side Settings

17.3.1 Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: MITSUBISHI ELECTRIC
• Controller Type: Set according to the Controller
Type to be connected.
• I/F: Interface to be used
• Driver:
Ethernet (MELSEC), Q17nNC, CRnD-700
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

17.3.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following:
1.1.2 I/F communication setting
17.3.2 Communication detail settings
Make the settings according to the usage environment.
GT16, GT14
3.
4.
Item
GOT NET No.
GOT PLC
*2
No.
GOT
Click!
IP Address
Subnet Mask
Default
*1
Gateway
Ethernet
Download Port
No.
*1
GOT
Communication
Port No.
Retry
Startup Time
Timeout Time
Delay Time
17. ROBOT CONTROLLER CONNECTION
Description
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 1)
Set the IP address of the GOT.
*1
(Default: 192.168.3.18)
Set the subnet mask for the sub
network.(Only for connection via
router)
*1
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the default
gateway where the GOT is
connected.(Only for connection via
router)
(Default: 0.0.0.0)
Set the GOT port No. for Ethernet
download.
(Default: 5014)
Set the GOT port No. for the
connection with the Ethernet module.
(Default: 5001)
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times out.
(Default: 3times)
Specify the time period from the GOT
startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination PLC.
(Default: 0ms)
17.3 GOT Side Settings
17
18
19
20
Range
1 to 239
1 to 64
0.0.0.0 to
255.255.255.255
21
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
22
1024 to 5010 to
5014 to 65534
(Except for 5011, 5012,
5013 and 49153)
1024 to 5010 to
5014 to 65534
(Except for 5011, 5012,
5013 and 49153)
23
0 to 5times
3 to 255sec
3 to 90sec
0 to 10000
(
10ms)
17 - 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents