Mitsubishi Electric GT1685 Connection Manual page 250

Got1000 series
Table of Contents

Advertisement

(4) MELSEC-A (GT10)
Item
Description
Set this item when change the transmission
speed used for communication with the
connected equipment.
(Default: 9600bps)
Transmission
When the setting exceeds the limit of the
Speed
connected equipment, communication is
performed at the fastest transmission
speed supported by the connected
equipment.
(5) MELSEC-WS
Item
Description
Set this item when change the transmission
speed used for communication with the
connected equipment.
(Default: 115200bps)
Transmission
When the setting exceeds the limit of the
Speed
connected equipment, communication is
performed at the fastest transmission
speed supported by the connected
equipment.
Set the number of retries to be performed
when a communication timeout occurs.
Retry
When receiving no response after retries,
the communication times out.
(Default: 3times)
Set the time period for a communication to
Timeout Time
time out.
(Default: 3sec)
Set this item to adjust the transmission
timing of the communication request from
Delay Time
the GOT.
(Default: 5ms)
6 - 32
6. DIRECT CONNECTION TO CPU
6.4 GOT Side Settings
POINT
POINT
POINT
(1) Communication interface setting by the Utility
(2) Precedence in communication settings
Range
HINT
HINT
HINT
Cutting the portion of multiple connection of the
controller
9600bps
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
0 to 5times
1 to 30sec
0 to 300 (ms)
The communication interface setting can be
changed on the Utility's [Communication Settings]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GT
User's Manual
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
By setting GOT internal device, GOT can cut the
portion of multiple connection of the controller. For
example, faulty station that has communication
timeout can be cut from the system.
For details of the setting contents of GOT internal
device, refer to the following manual.
GT Designer3 Version Screen Design Manual
(Fundamentals)
Disconnect the
faulty station

Hide quick links: