Mitsubishi Electric GT1685 Connection Manual page 808

Got1000 series
Table of Contents

Advertisement

Item
Description
GOT
Set the IP address of the GOT.
IP Address
(Default: 192.168.3.18)
IP Label
Set the IP Label of detail setting.
Set the subnet mask for the sub
network. (Only for connection via
router)
*1
Subnet Mask
If the sub network is not used,
the default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the GOT
Default
is connected. (Only for
*1
Gateway
connection via router)
(Default: 0.0.0.0)
Ethernet
Set the GOT port No. for
Download Port
Ethernet download.
*1
(Default: 5014)
No.
*1
Click the [Setting] button and perform the setting in the [GOT
IP Address Setting] screen.
POINT
POINT
POINT
Setting the FA transparent function of GX Works2
When connecting the GOT and the personal computer
in Ethernet connection, set the GOT IP address and
the Ethernet download port No. to the same as the
contents of PLC side I/F detailed setting of GOT.
23.6.4 Accessing by GX Works2
(c) Host (modem) setting
When communicating the GOT via modem, set the
interface of the GOT to be used in the
communication with the modem.
Item
Description
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 115200)
Set this item when change the data
length used for communication with
Data Bit
the connected equipment.
(Default: 8bit)
Specify the stop bit length for
Stop Bit
communications.
(Default: 1bit)
23 - 46
23. FA TRANSPARENT FUNCTION
23.5 GOT Side Settings
Range
Parity
0.0.0.0 to
255.255.255.255
-
Retry
0.0.0.0 to
255.255.255.255
Timeout Time
Initialization
0.0.0.0 to
255.255.255.255
Command
1024 to 5010,
5014 to 65534
(Except for 5011, 5012,
5013, 49153)
3.
POINT
POINT
POINT
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
Item
Description
Specify whether or not to perform a
parity check, and how it is performed
during communication.
(Default: Odd)
Set the number of retries to be
performed when a communication
timeout occurs.
(Default: 1time)
Set the time period for a
communication to time out.
(Default: 5sec)
Set the AT command to initialize the
modem.
*1
(Default:
AT&FE0%C0&K0&D0W2S0=1)
*1
The maximum number of characters of the AT command
differs according to the specification of the modem. When
the maximum number of characters of the AT command
which can be used in the modem is less than 255, set the
initialization command according to the specification of the
modem.
Click the [OK] button when settings are completed.
(1) Communication interface setting by Utility
The communication interface setting can be
changed on the Utility's [Communication Settings]
after downloading [Communication Settings] of
project data.
For details on the Utility, refer to the following
manual.
GT
User's Manual
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Range
None
Even
Odd
1time
5sec
Up to 255 one-byte
alphanumeric
characters