Mitsubishi Electric GT1685 Connection Manual page 391

Got1000 series
Table of Contents

Advertisement

(1) Network number setting switch
Network number
Description
setting switch
NETWORK NO.
X100
Network
No. setting
X10
(Network
No.1)
X1
: Necessary
*1
Specify the same network No. as that of the GOT.
*2
Do not specify a number between 240 and 255.
(2) Group number setting switch
Group number
Description
setting switch
Group No.
setting
GROUP.NO.
(No group
setting)
: Necessary
(3) Station number setting switch
Station number setting switch
Description
STATION.NO.
X10
Station number
setting
(Station No.1)
X1
: Necessary
*3
Do not set the same station No. as that of the GOT.
(4) LED indication select switch
LED indication select switch
Description
DISPLAY
LED indication
L
R
select
(F.L)
(R.L.)
: Necessary
Setting
Set
necessity at
value
GOT
connection
1
*1*2
: As necessary
: Not necessary
Setting
Set
necessity at
value
GOT
connection
0
(fixed)
: As necessary
: Not necessary
Setting
Set
necessity at
value
GOT
connection
1
*3
: As necessary
: Not necessary
Setting
Set
necessity at
value
GOT
connection
L (F.L.)
: As necessary
: Not necessary
10. MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)
(5) Mode setting switch
Mode setting switch
Mode setting
C
MODE
(Online)
0:ONLINE(A.R)
2:OFFLINE
: Necessary
(6) Condition setting switches
Condition setting
Setting
switches
switch
Network type
(PLC to PLC
SW1
net-work
(PC))
Station type
OFF ON
(Control
SW
SW2
station
1
(MNG))
2
Parameter
3
for using
4
SW3
(common
5
parameter
6
(PRM))
7
SW4
No. of
8
stations*1
SW5
SW6
Total B/W
points*1
SW7
SW8
Not used
: Necessary
*1
The MELSECNET/10 network module can be communicated
by default parameters.
For details, refer to the following manual.
Type MELSECNET/10 Network system (PLC to PLC
network) Reference Manual
POINT
POINT
POINT
When the switch setting (other than the LED indication
select switch) is changed
Turn the PLC CPU OFF then ON again, or reset the
PLC CPU.
10.4 PLC Side Setting
Setting
Set
necessity at
Description
value
GOT
connection
0
(fixed)
: As necessary
: Not necessary
Setting
Set
necessity at
Description
value
GOT
connection
OFF
(fixed)
ON
(fixed)
*1
OFF
(fixed)
OFF
(fixed)
OFF
(fixed)
OFF
(fixed)
: As necessary
: Not necessary
10 - 23
9
10
11
12
13
14
15
16