[Network parameter] of GX Developer
(1) Network parameter
Item
Network type
*1
Starting I/O No.
*2
Network No.
Group No.
*3
Station No.
Mode
Operation setting
Initial settings
Open settings
Router relay parameter
Station No.<->IP information
FTP Parameters
E-mail settings
Interrupt settings
*4
Redundant settings
Routing Parameters
: Necessary
*1
When using Q170MCPU, set the start I/O to 0070
*2
Specify the same network No. as that of the GOT.
*3
Do not set the same station No. as that of the GOT.
*4
Set when using Ethernet module in a redundant QnPRHCPU
system.
8 - 36
8. ETHERNET CONNECTION
8.4 PLC Side Setting
Setting
necessity at
Set value
GOT
connection
Ethernet (fixed)
0000
H
1
0 (fixed)
2
Online (fixed)
Refer to (2)
(Use default value)
Refer to (3)
: As necessary
: Not necessary
.
H
(2) Operation setting
Item
*1
Communication data code
IP address
*1
Initial timing
Send frame setting
*1
Enable Write at RUN time
TCP Existence confirmation
setting
: Necessary
*1
Because port No. 5001 is fixed, these items operate at the
following setting without relations to the setting given here.
• Communication
date code
• Initial timing
• Enable Write at
RUN time
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the PLC CPU,
operate the PLC CPU ether turning OFF and then ON
or resetting.
Setting
necessity at
Set value
GOT
connection
(Use default value)
192.168.0.19
(Use default value)
: As necessary
: Not necessary
: [Binary code]
: "Always wait for OPEN"
(Communication is applicable while
stopping the PLC CPU.)
: [Enable Write at RUN time] (Writing
Data is applicable while running the
PLC CPU.)