(3) Calculation example
(a) When connecting the GT15-J71BR13, GT15-RS4-9S (3 units), GT15-J71E71-100 (for the gateway
function) and a bar code reader (0.12 A) to the GT1575-V
Current supply capacity of GOT (A)
Since the calculated value is within the capacity of the GOT, they can be connected to the GOT.
(b) When connecting the GT15-J71BR13, GT15-RS4-9S (2 units), GT15-J71E71-100 (for the gateway
function) and a bar code reader (0.12 A) to the GT1585-S
Current supply capacity of GOT (A)
Since the calculated value exceeds the capacity of the GOT, such configuration is not allowed.
2.2
1.74
Total consumed current (A)
0.77+0.33+0.33+0.33+0.224+0.12=2.104
Total consumed current (A)
0.77+0.33+0.33+0.224+0.12=1.774