When connecting the GOT and personal
computer in Ethernet connection (GT16,
GT15 and GT14 only)
(1) Connecting the GOT and PLC in bus connection or
direct CPU connection
1.
Click the Connection Destination view
[Connection Destination]
name)] in the Navigation window of MT Works2.
2.
The [Transfer Setup] is displayed.
3.
Set the [Transfer Setup]:
PC side I/F
PLC side I/F
Other Station Setting
4.
Double-click [Ethernet Board] of the PC side I/F to
display [PC side I/F Ethernet Board Setting].
5.
Set the protocol to TCP. Network No. and Station No.
are not required to be changed (default) because they
are not used.
23 - 72
23. FA TRANSPARENT FUNCTION
23.6 Personal Computer Side Setting
[(Connection target data
: Ethernet Board
: GOT
: No Specification:
(For bus connection)
6.
Double-click [GOT] of the PLC side I/F to display
[PLC side I/F Detailed Setting of GOT].
7.
Set the IP address and port No. in [Ethernet detail
setting for PC and GOT connection].
Set the IP address and port No. to the same as the
Ethernet download setting.
23.5.1 (b) Ethernet download setting
8.
Check either of the followings in [Detail setting for
GOT and PLC connection].
Bus connection
[via GOT(Bus) transparent mode]
Direct CPU connection
Mark the [via GOT(direct coupled) transparent mode]
checkbox.
9.
The screen returns to [Transfer Setup]. Click
[Connection Test] to check if GX Developer has been
connected to the Motion controller (Q mode).