Mitsubishi Electric GT1685 Connection Manual page 408

Got1000 series
Table of Contents

Advertisement

(c) Routing setting
Up to 64 [Target Network No.]s can be set.
However, the same transfer network number
cannot be set twice or more (multiple times).
Therefore, the one that can access to other station
from the request source host GOT is 64 kinds of
[Target Network No.]s.
Item
Target Network No.
Relay Network No.
Relay Station No.
POINT
POINT
POINT
Routing parameter setting of request source
Routing parameter setting is also necessary for the
request source GOT.
For the setting, refer to the following.
11.3.3 Routing parameter setting
11 - 14
11. CC-Link IE CONTROLLER NETWORK CONNECTION
11.4 PLC Side Setting
Range
1 to 239
1 to 239
1 to 120
(2) [Controller Setting] of GT Designer3
Item
Network type
Network No.
Station No.
Group No.
Mode
Refresh Interval
Retry
Timeout Time
Delay Time
Monitor Speed
POINT
POINT
POINT
Network type of the GOT side
When the network is in the extended mode, be sure to
set the network type of the GOT side to [CC IE Control
extended mode].
For [Controller Setting], of GT Designer3, refer to the
following.
11.3.1 Setting communication interface
(Communication settings)
Set value
CC IE Control extended mode
1: Network No.1
2: Station No.2
0 (fixed)
Online (auto. reconnection)
1ms (Use default value)
3times (Use default value)
3sec (Use default value)
0ms (Use default value)
High (Normal) (Use default value)