Mitsubishi Electric GT1685 Connection Manual page 485

Got1000 series
Table of Contents

Advertisement

(2) Program condition (for FROM/TO instruction)
This program writes parameters to the buffer memory
when PLC CPU status changes from STOP to RUN
and automatically starts the data link with FROM/TO
instruction.
(a) I/O signal of CC-Link module
Control & Communication Link System Master/
Local Module Type AJ61BT11/A1SJ61BT11
User's Manual
(b) Devices used by user
Device
M100, M101
Flag for parameter setting
M102, M103
Flag for data link startup
D0
Number of connected modules
D1
Number of retry
D2
Automatic reconnection station count
D3
Operation specification in the case of CPU failure
Reserved station specification (Station No. 1 to
D4
Station No. 16)
Error invalid station specification (Station No. 1 to
D5
Station No. 16)
D6
Station data (first module)
D400
Error code in the case of data link startup failure
(c) Buffer memory settings used in the present
example
Buffer memory
address
Decimal (Hex)
1 (1
)
Number of connected modules
H
2 (2
)
Number of retry
H
Automatic reconnection station
3 (3
)
H
count
Operation specification in the
6 (6
)
H
case of CPU failure
Reserved station specification
16 (10
)
H
(Station No. 1 to Station No. 16)
Error invalid station specification
20 (14
)
H
(Station No. 1 to Station No. 16)
32 (20
)
Station data (first module)
H
*1
Details for the station data are shown below.
For 1) and 2), set the same station No. and number of station
occupied settings as those of the GOT.
For 3), the setting is fixed.
b15
to
b12
b11
to
b8
3)
2)
1)
Station No. (Set the same station No. as that of the GOT.)
01
to 40
: Station No. 1 to Station No. 64
H
H
2)
Number of stations occupied (Set the same setting of the
number of station occupied as that of the GOT.)
1
: Exclusive station 1
H
2
: Exclusive station 2
H
3
: Exclusive station 3
H
4
: Exclusive station 4
H
3)
Station type (2
: Set it to intelligent device station.)
H
0
: Remote I/O station
H
1
: Remote device station
H
2
: Intelligent device station (Incl. local station)
H
Application
Item
Set value
1 (1 module)
3 (3times)
1 (1 station)
0 (stop)
0 (No
specification)
0 (No
specification)
*1
2101
H
b7
to
b0
1)
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
9
10
11
12
13
14
15
16
13 - 45