Got Side Settings; Setting Communication Interface (Communication Settings); Communication Detail Settings - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

11.3 GOT side settings

11.3.1
Setting communication
interface (Communication
settings)
Set the channel of connecting equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: MITSUBISHI ELECTRIC
• Controller Type: Set according to the Controller
Type to be connected.
• I/F: Interface to be used
• Driver: CC-Link IE Controller Network
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

11.3.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
11.3.2 Communication detail settings
Make the settings according to the usage environment.
3.
4.
Item
Network
*4
Type
Network No.
Click!
Station No.
Mode Setting
Retry
Timeout
Time
Delay Time
Refresh
Interval
11. CC-Link IE CONTROLLER NETWORK CONNECTION
Description
Set the network Type
(Default: CC IE Control)
Set the network No.
(Default: 1)
Set the station No. of the GOT.
(Default: 1)
Set the operation mode of the GOT.
(Default:
Online (auto. reconnection))
Set the number of retries to be
performed when a communication
timeout occurs.
When no response is received after
retries, a communication times out.
(Default: 3times)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination PLC.
(Default: 0ms)
Set the number of refreshes to
secure the send/receive data in
station units during communication.
(Default: 1ms)
Valid when [Block data assurance
per station is available.] is checked
by the control station side network
parameters of the CC-Link IE
Controller Network.
11.3 GOT side settings
9
10
11
Range
• CC IE Control
12
• CC IE Control
extended mode
1 to 239
1 to 120
• Online
(auto.
13
reconnection)
• Offline
*1
• Test station
• Self-loopback
*1
test
• Internal self-
*1
loopback test
*1
• Line test
*1
• H/W test
14
0 to 5times
3 to 90sec
15
0 to 300ms
1 to 1000ms
16
11 - 9