Mitsubishi Electric GT1685 Connection Manual page 645

Got1000 series
Table of Contents

Advertisement

(3) Transmission baudrate setting switch
Transmission
baudrate setting
Description
switch
Specify the transmission speed.
(Default: 0)
(4) Condition setting switches
Condition
Setting
setting
Description
switch
switches
Specify input data status of the
SW1
data link error station.
(Default: OFF)
Specify the number of stations
SW2
occupied.
(Default: OFF)
POINT
POINT
POINT
(1) Switch setting example
For the switch setting example, refer to the
following.
18.5.2 CC-Link (ID) connection
(2) When the switch setting is changed
When changing the switch setting after mounting
the GT15-75J61BT13-Z type CC-Link
communication unit to the GOT, reset the GOT.
Set value
0: 156kbps
1: 625kbps
2: 2.5Mbps
3: 5Mbps
4: 10Mbps
Set value
OFF: Cleared
ON: Held
OFF: 1 station
ON: 4 stations
18. CNC CONNECTION
18.4 GOT Side Settings
17
18
19
20
21
22
23
18 - 15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents