Routing Parameter Setting - Mitsubishi Electric GT1685 Connection Manual

Got1000 series
Table of Contents

Advertisement

Item
Description
Set the number of refreshes to
secure the send/receive data in
station units during
communication.
Refresh
(Default: 1time)
Interval
Valid when [Secured data send/
Secured data receive] Is marked
by the control station side
network parameters of the
melsecnet/h network system.
Set the communication
transmission speed.
Transmission
(Default: 25Mbps)
Speed
When specifying [MNET/10
mode] as The network type, only
10mbps can be set applicable.
*1
For monitoring the QCPU redundant system, use QCPU of
function version D or later, with the upper five digits later than
"07102".
Also, use GX Developer of Version 8.29F or later.
*2
For details, refer to the following manual.
Q corresponding MELSECNET/H Network System
Reference Manual (PLC to PLC network)
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be
changed on the Utility's [Communication Settings]
after writing [Communication Settings] of project
data.
For details on the RS-422 conversion unit and the
GOT utility, refer to the following manual:
GT
User's Manual
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
9.3.3

Routing parameter setting

Up to 64 [Transfer Network No.]s can be set.
However, the same transfer network number cannot be set
twice or more (multiple times).
Therefore, the one that can access to other station from the
request source host GOT is 64 kinds of [Transfer Network
No.]s.
POINT
POINT
POINT
Routing parameter setting
When communicating within the host network, routing
parameter setting is unnecessary.
For details of routing parameters, refer to the following
manual.
Q corresponding MELSECNET/H Network
System Reference Manual (PLC to PLC
network)
Range
1 to 1000times
10Mbps/25Mbps
Transfer Network No.
Relay Network No.
Relay Station No.
POINT
POINT
POINT
(1) Routing parameter setting of relay station
(2) Parameter reflection function of MELSOFT
9. MELSECNET/H CONNECTION (PLC TO PLC NETWORK)
Item
1 to 239
1 to 239
1 to 64
Routing parameter setting is also necessary for
the relay station.
For the setting, refer to the following.
9.4 PLC Side Settings
Navigator
(a) The color of the cells for the items which are
reflected to GT Designer3 from MELSOFT
Navigator changes to green. Set items, which
are displayed in green cells, from the
MELSOFT Navigator.
(b) When the settings of Transfer network No.,
Relay network No. or Relay station No. are
reflected to the parameter from the MELSOFT
Navigator, those settings are added. Items set
in advance are not deleted.However, if the
target network No. overlaps, the item set in
advance is overwritten.
(c) The routing information is used manually by
the user when the data is created. Therefore,
after changing the network configuration by
MELSOFT Navigator, create a routing
information again. For details of the creation
of the routing information, refer to the
MELSOFT Navigator help.
9.3 GOT Side Settings
9
10
Range
11
12
13
14
15
16
9 - 11