10.3 GOT Side Settings

10.3.1 Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: MITSUBISHI ELECTRIC
• Controller Type: Set according to the Controller
Type to be connected.
• I/F: Interface to be used
• Driver:
When using the MELSECNET/H communication unit
MELSECNET/H
When using the MELSECNET/10 communication
unit
MELSECNET/10
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

10.3.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
10 - 10
10. MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)
10.3 GOT Side Settings
3.
4.
Click!
[Controller Setting] from the
10.3.2 Communication detail settings
Make the settings according to the usage environment.
(1) MELSECNET/H
Item
Description
Set the network type.
Network Type
(Default: MNET/H mode)
Set the network No.
Network No.
(Default: 1)
Set the station No. of the GOT.
Station No.
(Default: 1)
Set the operation mode of the
GOT.
Mode Setting
(Default:
Online (auto. reconnection))
Set the number of retries to be
performed when a communication
timeout occurs.
Retry
When no response is received
after retries, a communication
times out.
(Default: 3times)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination
Delay Time
PLC.
(Default: 0ms)
Range
• MNET/H mode
• MNET/10 mode
• MNET/H Extended
*1
mode
1 to 239
1 to 64
• Online
(Auto Reconnect)
• Offline
• Test between
*2
slave station
*2
• Self-loopback test
• Internal self-
loopback
*2
test
*2
• H/W test
0 to 5times
3 to 90sec
0 to 300ms