A30930 (N)
Power unit: Component trace has saved data
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
Trace data was saved in the component.
Remedy:
Not necessary.
Note:
For p7792= 1, the trace data of the component can be written to the memory card.
See also: p7792 (Upload component trace data)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F30950
Power unit: Internal software error
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, VECTOR_G
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Information about the fault source.
Only for internal Siemens troubleshooting.
Remedy:
- If necessary, upgrade the firmware in the power unit to a later version.
- contact the Hotline.
A30999 (F, N)
Power unit: Unknown alarm
Message value:
New message: %1
Message class:
Power electronics faulted (5)
Drive object:
B_INF, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm occurred on the power unit that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Alarm value (r2124, interpret decimal):
Alarm number.
Note:
If required, the significance of this new alarm can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the power unit by an older firmware version (r0128).
- upgrade the firmware on the Control Unit (r0018).
Reaction upon F:
Vector: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F31100 (N, A)
Encoder 1: Zero mark distance error
Message value:
%1
Message class:
Position/speed actual value incorrect or not available (11)
Drive object:
B_INF, ENC, VECTOR_G
Reaction:
Vector: ENCODER (IASC/DCBRK, NONE, OFF1, OFF2, OFF3, STOP2)
Infeed: NONE (OFF1, OFF2)
Acknowledge:
PULSE INHIBIT
Cause:
The measured zero mark distance does not correspond to the parameterized zero mark distance.
SINAMICS G130/G150