F30051
Power unit: Motor holding brake short circuit detected
Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A short-circuit at the motor holding brake terminals has been detected.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the motor holding brake for a short-circuit.
- check the connection and cable for the motor holding brake.
F30052
EEPROM data error
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
B_INF, VECTOR_G
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
EEPROM data error of the power unit module.
Fault value (r0949, interpret decimal):
0, 2, 3, 4:
The EEPROM data read in from the power unit module are incorrect.
1:
EEPROM data is not compatible to the firmware of the power unit application.
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
Re fault value = 0, 2, 3, 4:
Replace the power unit module or update the EEPROM data.
For fault value = 1:
The following applies for CU31x and CUA31:
Update the firmware \SIEMENS\SINAMICS\CODE\SAC\cu31xi.ufw (cua31.ufw)
F30053
FPGA data faulty
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
The FPGA data of the power unit are faulty.
Remedy:
Replace the power unit or update the FPGA data.
A30054 (F, N)
Power unit: Undervoltage when opening the brake
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
When the brake is being opened, it is detected that the power supply voltage is less than 24 V - 10% = 21.6V.
Alarm value (r2124, interpret decimal):
Supply voltage fault [0.1 V].
Example:
Alarm value = 195 --> voltage = 19.5 V
Remedy:
Check the 24 V voltage for stability and value.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1549