4 Faults and alarms
4.2 List of faults and alarms
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
5: standard gateway is also set at the PROFINET onboard interface.
6: the station name is also set at the PROFINET onboard interface.
7: IP address is located in the same subnet as the IP address of the PROFINET onboard interface.
Note:
For alarm value = 0, 1, 2, 7 the following applies: the configuration was not changed.
For alarm value = 5, 6 the following applies: The new configuration was however activated.
IE: Industrial Ethernet
See also: p8900 (IE Name of Station), p8901 (IE IP Address of Station), p8902 (IE Default Gateway of Station),
p8903 (IE Subnet Mask of Station)
Remedy:
- Check the required interface configuration (p8900 and following), correct if necessary, and activate (p8905).
or
- Reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).
See also: p8905 (IE Interface configuration)
A08562
PROFINET: Syntax error in configuration file
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A syntax error has been detected in the ASCII configuration file for the onboard PROFINET interface. The saved
configuration file has not been loaded.
Remedy:
- Check the interface configuration (p8920 and following), correct if necessary, and activate (p8925 = 1).
- Save the parameters for interface configuration (e.g. p8925 = 2).
or
- Reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).
See also: p8925 (PN interface configuration)
A08563
PROFINET: Consistency error affecting adjustable parameters
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A consistency error was detected when activating the configuration (p8925) for the PROFINET interface.
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists.
4: a cyclic PROFINET connection is not possible as DHCP is activated.
5: standard gateway is also set at the Industrial Ethernet interface (X127).
6: standard station name is also set at the Industrial Ethernet interface (X127).
7: IP address is located in the same subnet as the IP address of the Industrial Ethernet interface (X127).
Note:
For alarm value = 0, 1, 2, 3, 4, 7 the following applies: the configuration was not changed.
For alarm value = 5, 6 the following applies: The new configuration was however activated.
DHCP: Dynamic Host Configuration Protocol
See also: p8920 (PN Name of Station), p8921 (PN IP address of station), p8922 (PN Default Gateway of Station),
p8923 (PN Subnet Mask of Station)
1522
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A