4 Faults and alarms
4.2 List of faults and alarms
Fault value (r0949, interpret decimal):
129:
- safety parameters for monitoring channel 2 corrupted.
- drive with enabled safety functions was possibly copied offline using the commissioning software and the project
downloaded.
131: Internal software error on the Control Unit.
255: Internal Motor Module/Hydraulic Module software error.
Remedy:
- re-commission the safety functions.
- upgrade the Control Unit software.
- upgrade the Motor Module/Hydraulic Module software.
- replace the memory card or Control Unit.
For fault value = 129:
- activate the safety commissioning mode (p0010 = 95).
- adapt the PROFIsafe address (p9610).
- start the copy function for SI parameters (p9700 = D0 hex).
- acknowledge data change (p9701 = DC hex).
- exit the safety commissioning mode (p0010 = 0).
- save all parameters (p0977 = 1 or "copy RAM to ROM").
- carry out a POWER ON (power off/on) for all components.
Note:
MM: Motor Module
SI: Safety Integrated
F30657
SI P2: PROFIsafe telegram number invalid
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
The PROFIsafe telegram number set in p9811 is not valid.
When PROFIsafe is enabled (p9801.3 = 1), then a telegram number greater than zero must be entered in p9811.
Note:
This fault does not result in a safety stop response.
See also: p9611 (SI PROFIsafe telegram selection (Control Unit)), p60022 (PROFIsafe telegram selection)
Remedy:
Check the telegram number setting (p9811).
F30659
SI P2: Write request for parameter rejected
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The write request for one or several Safety Integrated parameters in monitoring channel 2 was rejected.
Note:
This fault does not result in a safety stop response.
Fault value (r0949, interpret decimal):
10: An attempt was made to enable the STO function although this cannot be supported.
11: An attempt was made to enable the SBC function although this cannot be supported.
13: An attempt was made to enable the SS1 function although this cannot be supported.
14: An attempt was made to enable the safe motion monitoring function with the higher-level control, although this
cannot be supported.
15: An attempt was made to enable the motion monitoring functions integrated in the drive although these cannot be
supported.
16: An attempt was made to enable the PROFIsafe communication - although this cannot be supported or the
version of the PROFIsafe driver used on both monitoring channels is different.
18: An attempt was made to enable the PROFIsafe function for Basic Functions although this cannot be supported.