M800V/M80V Series PLC Development Manual
6 Explanation of Built-in Editing Function (PLC On-board)
6.11 Basic Operation

6.11.4.4 Save the Sequence Program to the Internal ROM

The following diagram illustrates the procedure to save sequence programs, which have been edited and debugged, to the
internal ROM. The same procedure is executed whether using only one project or using multiple projects.
Procedure
Start
Main
Stop the PLC.
Main/ladder
PLC RUN/STOP
Main/NC file operation
Write the sequence
program to ROM.
ROM write
Complete
IB-1501614-B
Operation
Screen position
Menu button
NC FILE
PLC RUN/STOP
STOP EXECUTE
ROM WRITE
EXECUTE
330
Transition to the NC file operation
screen.
Display the PLC RUN/STOP popup
screen.
Stop the PLC.
Close the PLC RUN/STOP popup
screen.
The ROM write popup screen displays.
Execute the ROM write operation.