Mitsubishi Electric M800VW Series Manual page 49

Plc development
Hide thumbs Also See for M800VW Series:
Table of Contents

Advertisement

M800V/M80V Series PLC Development Manual
2 System Configuration of H/W
2.6 Outline of Digital Signal Output Circuit
Note
(1) When using an inductive load such as a relay, always connect a diode (voltage resistance 100V or more, twice or more
the load current) in parallel to the load.
Source output
Inductive load
Y
Diode
(2) When the rush current exceeds the maximum output current, always connect a protective resistor serially to the load to
suppress rush currents. Make sure that the current is less than the maximum output current including the momentary cur-
rent.
Source output
Load Resistor
Y
(3) Always keep the total sum of output current of each Y200 to Y207, Y208 to Y20F, Y210 to Y217, Y218 to Y21F, Y220 to
Y227, Y228 to Y22F, Y230 to Y237 and Y238 to Y23F less than 0.8 A.
0.2A or less per point
Y 200
Y 201
Y 202
Y 203
Total 0.8A
Y 204
or less
Y 205
Y 206
Y 207
Y 208
Y 209
Y 20A
Y 20B
Total 0.8A
Y 20C
or less
Y 20D
Y 20E
Y 20F
CAUTION
(1) When using an inductive load such as a relay, always connect a diode in parallel to the load to prevent a counter-
electromotive force.
(2) When the rush current exceeds the maximum output current, always connect a protective resistor serially to the
load to suppress rush currents.
IB-1501614-B
Y210
Y 220
Y211
Y 221
Y212
Y 222
Y213
Y 223
Y214
Y 224
Y215
Y 225
Y216
Y 226
Y217
Y 227
Y218
Y 228
Y219
Y 229
Y21A
Y 22A
Y21B
Y 22B
Y21C
Y 22C
Y21D
Y 22D
Y21E
Y 22E
Y21F
Y 22F
Total 3.8A or less
Y 230
Y 231
Y 232
Y 233
Total 0.8A
Y 234
or less
Y 235
Y 236
Y 237
Y 238
Y 239
Y 23A
Y 23B
Total 0.8A
Y 23C
or less
Y 23D
Y 23E
Y 23F
24
Total 0.8A
or less
Total 0.8A
or less