Basic Specifications - Mitsubishi Electric M800VW Series Manual

Plc development
Hide thumbs Also See for M800VW Series:
Table of Contents

Advertisement

M800V/M80V Series PLC Development Manual
5 Peripheral Development Environment (GX Works2)
5.5 Common Items

5.5.11.2 Basic Specifications

[Basic specifications list]
("[ ]" shows the name in built-in edit function)
Details
Sampling trace can be executed for each project.
Multi-project
Refer to (*6) for the timing of sampling when the multi-project is enabled.
The number between 1 and 8192 can be set. Note that, however, the total trace data size has to be smaller than
220 kilobytes.
Trace count
(The data size for a project depends on the number of usable projects.)
Refer to (*1) for trace data size calculation.
Trace count after trigger Sets the number smaller than the No. of traces.
Each scan
Detail
(Other notes are
Data acquisition timing
listed outside the
[trace point]
table. (*4)Refer to
(Each scan or specified
"(*4)" for details.
interval)
At the time of trig-
ger operation from
GX Works2
Trigger condition
Detail
[trigger point]
(Other notes are
(Two types of setting: "At
listed outside the
the time of trigger opera-
table. (*5)Refer to
tion from GX Works2" and
"(*5)" for details.
"Detail" are available.)
Up to 50 points of word device, 50 points of bit device can be set. Note that, however, the total trace data size
has to be smaller than 220 kilobytes. Refer to (*1) for trace data size calculation.
Trace device
(The data size for a project depends on the number of usable projects.)
Applicable device: Refer to (*3).
(*1) Trace data size calculation
The trace data size in one project varies with the number of multi-projects that can be used.
[Trace data size per project for the number of projects that can be used]
The number of projects that
can be used
6
5
4
3
2 projects
1
User safety sequence
For example, if the number of usable projects is 6, set the number of traces and the trace devices so that the trace data
size is 25 kilobytes (25600 bytes) or smaller. Trace data size will be calculated as follows.
[Trace data size (byte)] = [Size required for one trace (byte)] x [Number of traces]
Size required for one trace is calculated from the number of word devices, the number of bit devices for trace and the size
required for one trace of each device. When time information is added, 4 bytes per trace is required.
Specifications
Trace on scan of main processes.
Word device
Applicable device: Refer to (*2).
Setting condition: Set the value to be used for the condition and the
judgement. When the setting value becomes equal to the word device
value, or when the value of the word device changes judgement will be
effective and trigger is executed.
Bit device
Applicable device: Refer to (*2).
Setting condition: Set ↑ or ↓ . When the setting condition is satisfied,
trace is executed.
Executes trigger by GX Works2 operations.
Word device
Applicable device: Refer to (*2).
Setting condition: Sets the value to be used for judgement. When the
setting value becomes equal to the word device value, judgement will
be effective and trigger is executed. Refer to (*5) for when writing to the
device.
Bit device
Applicable device: Refer to (*2).
Setting condition: Set ↑ or ↓ . When the setting condition is satisfied,
trace is executed.
Maximum trace data size per project
25 kilobytes
32 kilobytes
44 kilobytes
64 kilobytes
103 kilobytes
220 kilobytes
220 kilobytes
103
IB-1501614-B

Advertisement

Table of Contents
loading

This manual is also suitable for:

M800vs seriesM80vw seriesM80v seriesM850vwM830vwM850vs ... Show all

Table of Contents