Fixed Signals; Ignoring Fixed Signals - Mitsubishi Electric M800VW Series Manual

Plc development
Hide thumbs Also See for M800VW Series:
Table of Contents

Advertisement

M800V/M80V Series PLC Development Manual
2 System Configuration of H/W

2.3 Fixed Signals

2.3 Fixed Signals
The connector pin Nos. in the input signals that are fixed are shown below.
Note that using the methods below can ignore fixed signals and change the allocations.
Signal name
Emergency stop
Stroke end +1
Stroke end +2
Stroke end +3
Stroke end +4
Stroke end +5
Stroke end +6
Stroke end +7
Stroke end +8
Reference position return near point de-
tection 1
Reference position return near point de-
tection 2
Reference position return near-point de-
tection 3
Reference position return near point de-
tection 4
Reference position return near point de-
tection 5
Reference position return near point de-
tection 6
Reference position return near point de-
tection 7
Reference position return near point de-
tection 8
Note
(1) When using the multi-part system and the 1st part system has 2 axes and the 2nd part system has 1 axis, the 1st axis in
the 2nd part system will correspond to the 3rd axis above.

2.3.1 Ignoring Fixed Signals

The fixed signals can be used as other signals by ignoring them with file registers R248 and R272.
Device
Signal name
EMG of main unit Stroke end -1
X28
Stroke end -2
X29
Stroke end -3
X2A
Stroke end -4
X2B
Stroke end -5
X6C
Stroke end -6
X6D
Stroke end -7
X6E
Stroke end -8
X6F
X18
X19
X1A
X1B
X5C
X5D
X5E
X5F
17
Device
X20
X21
X22
X23
X64
X65
X66
X67
IB-1501614-B