YASKAWA GA700 Series Technical Manual page 26

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

1.2 Verifying the Drive Model and Nameplate
Model
4002
4004
4005
4007
4009
4012
4018
4023
4031
4038
4044
4060
4075
4089
4103
4140
4168
4208
4250
4296
4371
4389
4453
4568
4675
26
Table 1.4 Three-Phase AC 400 V Class (Input Voltage ≥ 460 V)
Heavy Duty Rating (HD)
[C6-01 = 0]
(Default)
Maximum Applicable Motor
Output
HP
3/4
1
2
3
4
5
7 1/2
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
350
400
-
E1-01 [Input AC Supply Voltage] ≥ 460
Maximum Applicable Motor
Rated Output Current
A
1.6
2.1
3.4
4.8
6.9
7.6
11
14
21
27
34
40
52
65
77
96
124
156
180
240
302
361
414
477
-
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Normal Duty Rating (ND)
[C6-01 = 1]
Rated Output Current
Output
HP
1
2
3
4
5
7 1/2
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
350
400
450
-
A
2.1
3.4
4.8
6.9
7.6
11
14
21
27
34
40
52
65
77
96
124
156
180
240
302
361
414
477
515
-

Advertisement

Table of Contents
loading

Table of Contents