YASKAWA GA700 Series Technical Manual page 24

Ac drive for industrial applications
Hide thumbs Also See for GA700 Series:
Table of Contents

Advertisement

1.2 Verifying the Drive Model and Nameplate
No.
1
Drive
2
Product series
3
Region code
• A: Japan
• B: China
• C: Europe
• D: India
• K: Korea
• T: Asia (Singapore and Taiwan)
• U: Americas
4
Input power supply voltage
• 2: Three-Phase AC 200 V Class
• 4: Three-Phase AC 400 V Class
5
Rated output current
Note:
Refer to the tables for the rated output current by model.
6
EMC noise filter
• A: No internal EMC filter
• B: Internal category C3 EMC filter
7
Protection design
• B: IP20
8
Environmental specification (Reserved)
9
Design revision order
10
Control circuit terminal board (Reserved)
11
Option (connector CN5-A) (Reserved)
12
Option (connector CN5-B) (Reserved)
13
Option (connector CN5-C) (Reserved)
14
Keypad (Reserved)
15
Special applications (Reserved)
Rated Output Current
Table 1.2
to
Table 1.4
give the rated output current values.
Note:
• These output current values are applicable for drives that operate at standard specifications.
• Derate the current in applications that:
–Increase the carrier frequency
–Have high ambient temperature
–Install drives side-by-side.
• Use C6-01 [Normal / Heavy Duty Selection] to select Normal Duty rating (ND) or Heavy Duty rating (HD).
Model
2004
2006
2010
2012
2018
2021
2030
2042
24
Table 1.1 Model Number Details
Table 1.2 Three-Phase AC 200 V Class
Heavy Duty Rating (HD)
[C6-01 = 0]
(Default)
Maximum Applicable Motor
Output
kW
0.55
0.75
1.5
2.2
3
4
5.5
7.5
Description
Maximum Applicable Motor
Rated Output Current
A
3.2
5
8
11
14
17.5
25
33
YASKAWA SIEPC71061705H GA700 Series Technical Manual
Normal Duty Rating (ND)
[C6-01 = 1]
Rated Output Current
Output
kW
0.75
1.1
2.2
3
4
5.5
7.5
11
A
3.5
6
9.6
12.2
17.5
21
30
42

Advertisement

Table of Contents
loading

Table of Contents