This section explains the two run command modes of the power regenerative unit. Select the mode according to the application.
Auto Run
Auto run is the mode in which the power regenerative unit detects any increase/decrease of the bus voltage and performs an auto run/stop if the
terminal S2-SC is "closed."
When the DC voltage is less than the voltage set at the auto run/stop level, the RC5 will stop after the preset time value in parameter C8-20 is passed
(default: 1 sec).
Figure 4.6
Drive Status
DC Bus Voltage
Regenerative Unit
Current at Power Side
Manual Run
Manual run is the mode in which the RC5 starts running when the terminal S1-SC is "closed," and stops one second after S1-SC is "open."
Figure 4.7
Drive Status
DC Bus Voltage
MANUAL RUN
Regenerative Unit
Run Status
Current at Power Side
Build a sequence so that the run commands of the power regenerative unit and the inverter are turned ON at the same time.
44
Auto Run
Regeneration
ON
AUTO RUN
RUN
Run Status
Figure 4.6 Time chart of the Auto Run Mode
Auto Run
Regeneration
ON
RUN
Figure 4.7 Time chart of the Manual Run mode
AC Power Supply Voltage x 1.35
AC Power Supply Voltage x 1.35
YASKAWA ELECTRIC TOEP C710656 01C YASKAWA - RC5 Instruction Manual