Group 3.12: Pid Controller - Danfoss VACON 3000 Application Manual

Table of Contents

Advertisement

VACON® 3000
Application Guide
Index
Parameter
P3.11.5
FUNCT Button Configuration
Motor speed filter time
P3.11.6
The default value in the US is 1.
1

4.5.12 Group 3.12: PID Controller

Table 77: PID Controller Basic Settings
Index
Parameter
P3.12.1.1
PID Gain
P3.12.1.2
PID Integration Time
P3.12.1.3
PID Derivation Time
P3.12.1.4
Process Unit Selection
P3.12.1.5
Process Unit Min
P3.12.1.6
Process Unit Max
P3.12.1.7
Process Unit Decimals
P3.12.1.8
Error Inversion
P3.12.1.9
Dead Band
P3.12.1.10
Dead Band Delay
Table 78: Setpoint Settings
Index
Parameter
P3.12.2.1
Keypad setpoint 1
P3.12.2.2
Keypad setpoint 2
P3.12.2.3
Setpoint ramp time
P3.12.2.4
PID select setpoint
Danfoss A/S © 2021.09
Min
Max
0
15
Min
Max
Unit
Default
0.00
1000.00
%
100.00
0.00
600.00
s
1.00
0.00
100.00
s
0.00
1
38
1
Varies
Varies
Varies
0
Varies
Varies
Varies
100
0
4
2
0
1
0
Varies
Varies
Varies
0
0.00
320.00
s
0.00
Min
Max
Varies
Varies
Varies
Varies
0.00
300.0
Varies
Varies
Unit
Default
ID
15
1195
s
0.00
4026
ID
Description
118
119
132
1036
1033
1034
1035
340
0 = Normal (Feedback < Setpoint -> Increase
PID output)
1 = Inverted (Feedback < Setpoint -> De-
crease PID output)
1056
1057
Unit
Default
ID
Varies
0
167
Varies
0
168
s
0.00
1068
DigIN Slot0.1
1047
AB319735759636en-000101 / DPD01822 | 73
INU Application
Description
2 = 3x3 sections
B0 = Local / Remote
B1 = Control Page
B2 = Change Direction
B3 = Quick Edit
Description
OPEN = Setpoint 1
CLOSED = Setpoint 2