8.2.12.7 Fault Code 14, ID 137 - Overvoltage Protection Circuit Temperature (Fault)
Cause
Too high an output capacitance or a ground fault in the floating network.
Troubleshooting
Check the cables and the motor.
8.2.12.8 Fault Code 14, ID 138 - AC Drive Overtemperature (Fault)
Cause
Output filter temperature is too high.
Troubleshooting
Check the motor cables and the motor.
Check the correct amount and flow of cooling air.
Check the ambient temperature.
8.2.12.9 Fault Code 14, ID 139 - AC Drive Overtemperature (Fault)
Cause
Brake chopper temperature is too high.
Troubleshooting
Check the correct amount and flow of cooling air.
Check the heat sink of the brake chopper for dust.
Check the ambient temperature.

8.2.13 Fault Code 15 - Motor Stall

8.2.13.1 Fault Code 15, ID 140 - Motor Stall
Cause
The motor stalled.
Troubleshooting
Check the motor and the load.

8.2.14 Fault Code 16 - Motor Overtemperature

8.2.14.1 Fault Code 16, ID 150 - Motor Overtemperature
Cause
There is too heavy a load on the motor.
Troubleshooting

8.2.15 Fault Code 17 - Motor Underload

8.2.15.1 Fault Code 17, ID 160 - Motor Underload
Cause
There is not a sufficient load on the motor.
Troubleshooting
Check the load.
Check the parameters.
Check the dU/dt and sine wave filters.
Danfoss A/S © 2021.09
Fault tracing
AB319735759636en-000101 / DPD01822 | 283