Fault Code 2 - Overvoltage - Danfoss VACON 3000 Application Manual

Table of Contents

Advertisement

VACON® 3000
Application Guide
8.2.1.3 Fault Code 1, ID 4 - Phase Overcurrent
Cause
The phase current is too high.
Troubleshooting
Check the loading.
Check the motor.
Check the cables and connections.
Make an identification run.
Set the acceleration time longer (P3.4.1.2 and P3.4.2.2).

8.2.2 Fault Code 2 - Overvoltage

8.2.2.1 Fault Code 2, ID 10 - Overvoltage (Hardware Fault)
Cause
The DC link voltage is higher than the limits.
too short a deceleration time
high overvoltage spikes in the supply
Troubleshooting
Set the deceleration time longer (P3.4.1.3 and P3.4.2.3).
Use a brake chopper. It is available as an option.
Activate the overvoltage controller.
Check the input voltage.
8.2.2.2 Fault Code 2, ID 11 - Overvoltage (Software Fault)
Cause
The DC link voltage is higher than the limits.
too short a deceleration time
high overvoltage spikes in the supply
Troubleshooting
Set the deceleration time longer (P3.4.1.3 and P3.4.2.3).
Use a brake chopper. It is available as an option.
Activate the overvoltage controller.
Check the input voltage.
8.2.2.3 Fault Code 2, ID 13 - DC+ Overvoltage
Cause
The positive DC-link voltage is higher than the limits.
too short a deceleration time
high overvoltage spikes in the supply
Troubleshooting
Set the deceleration time longer (P3.4.1.3 and P3.4.2.3).
Use a brake chopper. It is available as an option.
Activate the overvoltage controller.
Check the input voltage.
270 | Danfoss A/S © 2021.09
Fault tracing
AB319735759636en-000101 / DPD01822